Fire and Life Safety Pre-Inspection Checklist

The list below helps owners and property managers check important safety items before a Fire and Life Safety Inspection. Utilize the checklist to systematically review each aspect of the inspection, ensuring all points are thoroughly evaluated and documented for accuracy and completeness. We hope this information will assist you in achieving a successful inspection.

FACILITY:
Property address number visible & legible per Township Ordinance.
Outside Fire Lanes are Clear: if present
FDC Connection is Accessible: Not obstructed by trees, parked cars, bushes etc. and appropriate thread for the fire department.: if present.
FDC Connection is marked: if present
Site Hydrants are Clear: if present
Site Hydrants are Marked: if present
Standpipes(s) are Accessible: if present
Standpipe(s) are Marked: if present
Information Knox Box is properly updated. Working keys and up to date contact information available at the time of fire inspection.
Evacuation plans posted, restaurants, schools, daycares, and worship buildings.
Outside Smoking Areas are clear, if present

EXITS:
Emergency Exits are Accessible
Exit doors operate without difficulty Must be easy to open and open with no special knowledge or force.
Exit doors are clearly marked
Exit doors/aisles are not obstructed. No storage in exit pathways or in front of exit doors
Exit doors are not locked during working hours
Exit signs are illuminated
Proper installation of exit signs. Exit doors/pathways clearly identified. Exit doors shall have signage located above all doors
Emergency Lights are Working. Exit signage operational, battery backup operational and properly maintained

STORAGE:
Hallways are clear of items
No under stairwell storage
Heating appliances maintain safe clearances
No combustible materials excessively stored near open flame, heat/electrical sour
Dumpster/Garbage area safe distance away from building and combustibles. Dumpster is a minimum of 5 feet from building; with closable lid
Excess Garbage is not present
No storage within 24 inches of ceiling
No storage within 18 inches of sprinkler heads
No storage present in exit corridors/exit stairways
Flammable liquids stored in flammable liquid storage cabinet
Compressed gas cylinders properly secured

FIRE AND SMOKE SPREAD:
No missing/damaged ceiling tiles
All Wall/ceiling penetrations have adequate fire stop
No Fire doors blocked open
Fire doors properly close or latch.

ELECTRICAL HAZARDS:
No Electrical cords extend through walls and ceilings
Door to electrical room labeled.
No combustible storage in electrical room
All circuits are labeled within panel boards
Electrical panels have blank breaker covers
The electrical panel box is properly covered
Electrical panel access is not obstructed. Electrical panel boards must have a 36' wide x 78' high clear working space, no obstructions
Electrical cords do not create tripping hazards
Electrical outlets within 6 feet of wet area include GFCI protection
Electrical outlet covers are not missing or damaged
Electrical outlets switch plates are not missing or damaged
Electrical junction boxes are properly covered
No exposed/unsafe electrical wiring
Extension cords not used as permanent wiring
No "daisy chain" of multiplug adapters, power strips, or extension cords. Extension cords may not extend through walls, under carpets, or under doors

FIRE PREVENTION & DETECTION EQUIPMENT:
Fire extinguisher inspection is current. Extinguishers must be inspected and tagged by a third-party fire protection contractor
Adequate fire extinguishers: within 75 feet travel distance from anywhere in the occupancy
Fire extinguishers mounted or in cabinet. Top of extinguisher not higher than 5 feet from floor
Fire extinguishers’ access is not obstructed. Extinguishers not blocked in any way
No damaged/missing pin/missing tamper seal or discharged fire extinguish
Alarm System Inspection. Fire alarm system must be operational; current annual test and inspection record are available for review
Fire alarm panel not obstructed and/or damaged
Pull stations not obstructed and/or damaged
Smoke/heat detectors not obstructed and/or damaged
Adequate installation of smoke/heat detectors
No obstructed or damaged fire alarm notification devices(horns/bells/strobes)
Kitchen Hood Systems Service/Inspection. Kitchen hood suppression systems system must be operational; current test and inspection record available for review
Class K extinguisher required for kitchens equipped with hood systems
Sprinkler System Annual Test. Fire sprinkler systems must be operational; current annual test and inspection record available for review
Fire Pump Annual Test. Fire pump must be operational; current annual test and inspection record available for review
No missing sprinkler head or piping escutcheons
No signs of defects or damage to any protective systems